A commission will weigh 17 conditions Wednesday for the data center planned at the old 3M campus on RM 2222

A draft Environmental Commission recommendation would cap SB Energy's River Place project at 70 megawatts, bar drinking water for cooling and add noise monitors at three schools. The council's first data center rules could come Dec. 3.

The city's Environmental Commission meets at 6 p.m. Wednesday, Nov. 18, and the last item on its agenda is a recommendation to the City Council on the data center being built on the former 3M campus at 6801 River Place Boulevard, off RM 2222 in District 10. Commissioners Richard Brimer, Annie Fierro and David Sullivan sponsored it.

The draft recommendation, posted with the agenda, describes the project this way: SE Cosmos LLC, an affiliate of SB Energy, is converting the roughly 156-acre campus "into a data center computing facility with about 50 MW of critical IT load and about 70 MW of total power."

What the draft asks the council to do

The draft lists 17 steps. Among them:

  • Power cap. Hold the site to 50 megawatts of IT load and 70 megawatts in total unless a public hearing is held on an increase.
  • Water. No drinking water for cooling; require a closed-loop, air-cooled system.
  • Reports. Quarterly public memos to the council and the commission on the facility's water and energy demand, and separately on air quality.
  • Noise. Round-the-clock noise and vibration monitoring within a mile, with stations at River Place Elementary, Four Points Middle and Vandegrift High.
  • Air permits. Direct the city manager to oppose state air permits for backup generators and new uses at the site.
  • Grid emergencies. Require the facility to curtail operations when the governor, ERCOT or local authorities declare an electrical emergency.
  • Fire. A wildfire plan for the property, and more training and equipment for Austin Fire Stations 39 and 31 for lithium-ion battery fires and diesel spills that could reach the Bull Creek watershed.
  • Wildlife and land. Dark-sky and bird-friendly design, an updated environmental study that maps karst features that vibration could affect, and enforcement of the 1984 and 1986 ordinances that govern the site.

The draft notes that the campus abuts Balcones Canyonlands Preserve land, home to the endangered golden-cheeked warbler, and that the preserve's management plan names light and noise as harmful to the birds. The vote count is blank; commission recommendations are advice to the council.

What has been said about the project

The Austin Free Press reported that an Aug. 31 filing by SB Energy with the Securities and Exchange Commission said the campus could host up to 50 megawatts of IT capacity and was leased "primarily for data centers and office buildings," while a city representative said the city's best information was a research and development center. The first tenant is Graphcore, which shares SB Energy's parent company, SoftBank. SB Energy told neighbors it would use closed-loop cooling and "will not consume more water than the previous tenant," the outlet reported. The site already had its zoning and building permits.

What our records add

Where the council heard about it. At its Aug. 25 work session, Council Member Marc Duchen, whose district includes the site, said the council had been told until recently that the campus would be used for "advanced R and D," and that material the company put out describing "a single tenant wholesale data center with a 50 megawatt critical IT load" was, the council was told, a mistake. He asked Austin Energy and Austin Water for periodic reports on big new customers. Staff told the council the same morning that the utility knew of no hyperscale data center requests.

The vote that started the rules. Two days later the council approved, 11-0, a resolution to write zoning and business rules for data centers and to hear from staff before approving any request above 20 megawatts of power or 85 million gallons of water a year. Duchen suggested making data centers a conditional use in some zones in the meantime: "if you walk like a data center and you quack like a data center, you may actually be" one.

What comes next on rules. An Oct. 28 staff memo, covered here, proposes business rules for large data centers for a possible Dec. 3 council vote and zoning rules in spring 2027. Council Member Mike Siegel told the Free Press the city cannot pass retroactive zoning to force a permitted project to be taken apart.

The preserve. The city's federal permit for the Balcones Canyonlands Preserve has expired, and Austin Water told a council committee that renewal will take four to five years.

What's next

  • Wednesday, Nov. 18, 6 p.m.: Environmental Commission, Permitting and Development Center, Room 1405. The same night, the Joint Sustainability Committee is set to vote on a recommendation on zoning for data centers.
  • Nov. 20: The Dec. 3 council agenda is due to be posted.